Inhibited Propylene Glycol 20/80 is a ready-to-use coolant of 20% propylene glycol by weight in deionized water with a nitrite-containing OAT corrosion inhibitor, freeze point approx. 19 °F (-7 °C). Data center, HVAC and facility teams use it in indoor closed loops: CDU technology cooling system (TCS) loops, rear-door heat exchangers and chillers. It comes in sizes from 1 quart to 55-gallon drums and 330-gallon IBC totes, starting at $16.65 (1 quart), and is not regulated by DOT.
The inhibitor package combines sodium nitrite, sodium molybdate, sodium benzoate and triethanolamine with organic-acid inhibitors, formulated for steel, cast iron, copper, brass and solder. Blended at our Taylor, TX facility.
Applications
- Data center liquid cooling secondary loops
- Coolant distribution unit (CDU) technology cooling system (TCS) loops
- Rear-door heat exchanger loops
- HVAC chillers & hydronic heating loops
- Light freeze protection, to approx. 19 °F (-7 °C)
Specifications
-
Composition: propylene glycol 19.5–20.5% by weight (w/w); corrosion inhibitor package 1.8–2.2%; deionized water balance
-
CAS: 57-55-6 (PG), 7732-18-5 (Water); product is a mixture
-
Nitrite (as NO2): 480 ppm min.
-
Density: 1.015–1.020 g/cm³ at 20 °C (calculated)
-
Density: approx. 1.02 g/mL (8.5 lb/gal)
-
pH: reported on the lot Certificate of Analysis (typically 7.0–9.0)
-
Reserve alkalinity: reported on the lot COA
-
Freeze point: approx. 19 °F (-7 °C); specification 20 °F (-6.7 °C) max
-
Boiling point: approx. 214 °F (101 °C)
-
Appearance: clear, colorless to pale yellow liquid; not dyed (dye available on request)
Documentation
Handling
Not classified as hazardous under GHS and not regulated for transport by DOT. Contains sodium nitrite: install as a fresh fill after draining and flushing, do not mix with phosphate-, silicate- or nitrite-free coolants, keep away from strong acids, and avoid galvanized (zinc) surfaces. Refer to the Safety Data Sheet (SDS) for full handling information.
Available sizes: 1 quart through 330-gallon IBC tote. Bulk loads quoted on request.
Not for: direct or incidental food contact, potable water, open recirculation, automotive crankcase, or single-pass cooling.
Frequently asked questions
What is Inhibited Propylene Glycol 20/80?
A ready-to-use heat-transfer fluid: propylene glycol 19.5–20.5% by weight in deionized water, with a nitrite-containing hybrid organic-acid (OAT) corrosion inhibitor package at 1.8–2.2%. The package combines sodium nitrite, sodium molybdate, sodium benzoate and triethanolamine with organic-acid inhibitors. It is blended in Taylor, Texas, and is not dyed.
What is the freeze point of 20% propylene glycol?
The freeze point is approx. 19 °F (-7 °C) at 20% propylene glycol by weight; the specification is 20 °F (-6.7 °C) max. The percentage is by weight, not by volume, so compare it against weight-percent freeze tables.
Should I choose PG 20/80, 25/75 or 30/70?
20/80 carries the least glycol in the line, so it suits indoor closed loops that do not see freezing temperatures, such as CDU technology cooling loops and rear-door heat exchangers inside a conditioned building. If piping, dry coolers or equipment can get near 20 °F, choose 25/75 or 30/70, which carry more glycol and freeze at lower temperatures.
Does it contain nitrite?
Yes. The inhibitor package contains sodium nitrite; the specification is nitrite 480 ppm min. (as NO2). It is not a nitrite-free coolant, so it does not meet a specification that requires one.
Is it hazardous or DOT regulated?
It is not classified as hazardous under OSHA HCS / GHS and is not regulated for transport by DOT, so it ships without a hazmat surcharge. It is not for food contact or potable water. See the Safety Data Sheet for handling guidance.
Which metals is it compatible with?
The inhibitor package is formulated for steel, cast iron, copper, brass and solder. Avoid galvanized (zinc) surfaces and strong acids. Install it as a fresh fill after draining and flushing; do not mix it with phosphate-, silicate- or nitrite-free coolants.
How do I top off or dilute it?
It is supplied ready to use, so do not dilute it further. Top off with the same 20/80 premix to keep glycol and inhibitor on spec; adding water alone lowers both.
Are the SDS, TDS and COA available?
Yes. The Safety Data Sheet (English, French, Spanish and Japanese) and the Technical Data Sheet are published on this page. A lot-specific Certificate of Analysis is available on request at no charge; pH and reserve alkalinity are reported on it.
What sizes are available and what does it cost?
1 quart, 1 gallon, 4-gallon case, 5 gallon, 15- and 55-gallon drums, and 275- and 330-gallon IBC totes, plus multi-packs and pallets. Prices start at $16.65 (1 quart); drum and tote prices are on the size selector. For larger quantities contact sales@alliancechemical.com.